Contact us: +49 9321 2680 -201

PRODUCT DETAILS

TGA Box

TGA Box_DC Combiner

DC Combiner

with integrated safety devices
  • String collection and protection (up to 32 inputs)
  • DC switch operated from outside/inside
  • String monitoring
  • Up to 1500V DC

Technical Data

Housing

Installation

Outdoor / Indoor

UN resistance

Yes

Material

PC/PBT mix

Fire properties

Glow wire test 650°C

Colour scheme

RAL 7035

Mounting

Wall

Dimensions & Weight

Housing (width/height/depth)

775/715/345mm

Weight

45kg

Input parameters

DC voltage

<= 1500 V

Number of DC inputs

3 to 32+

3 to 32 -

String connection

Cable gland, max. 10 mm²

String current

Max. 21A (With single string monitoring max. 20A)

String fuse

Max. 30A

DC toal current

Max. 250A

Output parameters

Main connection

Cable lug M12/M16

Cable fitting for string connection

M32 to M50

Grounding connection

Protection clamp 1,5mm²-3,5mm²

Standards

CE

Conform

Protection class and ambient conditions

Protection class in accordance with EN60529

IP 65

Permissible ambient temperature

-20 °C to +40 °C

Rel. Luftfeuchte nicht kondensierend

15% to 90%

Altitude above sea level

Max. 2.000 m

Additional properties

Surge protection

Typ 2

Optional

Single string monitoring

Up to 32 Strings (32 measurement channels)

Double string monitoring

Up to 32 Strings (16 measurement channels)

Surge protection

Typ1 & 2 combined

String connection

MC4 compatible, max. 10 mm²

String connection

Cage clamp terminal, max. 10 mm²

DC switch disconnector

Operation from outside / inside

DC switch disconnector mountings

For example alarm switch

Permissible ambient temperature

-20 °C to +50 °C

 

  • Technical Data