TGA Box
DC Combiner
with integrated safety devices
- String collection and protection (up to 32 inputs)
- DC switch operated from outside/inside
- String monitoring
- Up to 1500V DC
Technical Data
Housing |
|
Installation |
Outdoor / Indoor |
UN resistance |
Yes |
Material |
PC/PBT mix |
Fire properties |
Glow wire test 650°C |
Colour scheme |
RAL 7035 |
Mounting |
Wall |
Dimensions & Weight |
|
Housing (width/height/depth) |
775/715/345mm |
Weight |
45kg |
Input parameters |
|
DC voltage |
<= 1500 V |
Number of DC inputs |
3 to 32+ 3 to 32 - |
String connection |
Cable gland, max. 10 mm² |
String current |
Max. 21A (With single string monitoring max. 20A) |
String fuse |
Max. 30A |
DC toal current |
Max. 250A |
Output parameters |
|
Main connection |
Cable lug M12/M16 |
Cable fitting for string connection |
M32 to M50 |
Grounding connection |
Protection clamp 1,5mm²-3,5mm² |
Standards |
|
CE |
Conform |
Protection class and ambient conditions |
|
Protection class in accordance with EN60529 |
IP 65 |
Permissible ambient temperature |
-20 °C to +40 °C |
Rel. Luftfeuchte nicht kondensierend |
15% to 90% |
Altitude above sea level |
Max. 2.000 m |
Additional properties |
|
Surge protection |
Typ 2 |
Optional |
|
Single string monitoring |
Up to 32 Strings (32 measurement channels) |
Double string monitoring |
Up to 32 Strings (16 measurement channels) |
Surge protection |
Typ1 & 2 combined |
String connection |
MC4 compatible, max. 10 mm² |
String connection |
Cage clamp terminal, max. 10 mm² |
DC switch disconnector |
Operation from outside / inside |
DC switch disconnector mountings |
For example alarm switch |
Permissible ambient temperature |
-20 °C to +50 °C |
- Technical Data
- Download