TGA Box TÜV
DC Combiner
with integrated safety devices
- String collection and protection (up to 32 inputs)
- DC isolator operated from outside/inside
- String monitoring (optional)
- Up to 1000V DC
- TÜV certified
Application area
Technical Data
General Data |
|
DC voltage |
Max. 1000 V |
DC short circuit current per input |
Max. 7,5 A |
DC Breaking & making capacity (according to EN60947-3) |
200 A |
Nominal current (I nom) per input |
Max. 6,24 A |
Short curcuit current |
< 375A |
Grounding (DC) |
Floating positive and negative |
Switch handle type |
External handle (outside enclosure) |
Housing |
|
Installation |
Outdoor / Indoor |
UV resistance |
Yes |
Material |
Polyester, fiberglass reinforced |
Colour scheme |
RAL 7035 |
Mounting |
Wall |
Dimensions & Weight |
|
Housing (width/height/depth) |
750/1000/320mm |
Weight |
50kg |
Input parameters |
|
Number of DC inputs |
32 (+&- being one input) |
Input cables |
2,5mm² – 6mm² |
Inputcables entrance through |
Cable gland up to 10mm² |
Fuse type |
10x38mm |
Location of fuses |
Negative side or positive side / Negative side and positive side |
Fuse link nominal current (I nom) |
20 A |
Fuse link time current characterisic |
gPV (EN 60269-6) |
Output parameters |
|
Number of DC outputs |
1x Plus / 1x Minus (+&- being one output) |
Output cables |
Max. 120 mm² |
Output cables casing feed through |
M40, cable outer Ø: 19-28 mm |
RS-485 cables |
0,5mm² – 2,5mm² |
RS-485 cables |
M20, cable outer Ø: 7-13 mm |
Grounding connection |
Min. 16 mm² |
Grounding cable casing feed-through |
M20, cable outer Ø: 7-13 mm |
Monitoring |
|
Values |
Input current, voltage and temp. |
Monitoring type |
Measurement of two combined inputs |
Power supply |
24 VDC (6 A fuse required) |
Standards |
|
CE |
Conform |
Protection class and ambient conditions |
|
Standards and regulations |
EN 61439-2 |
Protection class in accordance with EN60529 |
IP 54 |
Permissible ambient temperature |
-20 °C to +50 °C |
Rel. humidity non-condensing |
15% to 90% |
Altitude above sea level |
Max. 2.000 m |
Additional properties |
|
Surge protection |
Typ 2 (auxiliary contact) |
Optional |
|
DC input cables casing feed through |
MC4 (6 mm²) |
DC switch disvonnector |